Hyper Mist System Fixed Fire Fighting System SOLAS Regulation

 > Cargo ships 2000 GT and above should have this system.

> Machinery space above 500 m3 volume  required an additional fixed fire fighting system.

>  It must have an independent power source or having connection from emergency switchboard 

> The number and arrangement of the nozzles shall be such as to ensure an effective average distribution of water of at least 5 l/m2/min in the spaces to be protected.

> Precautions shall be taken to prevent the nozzles from becoming clogged by impurities in the water or corrosion of piping, nozzles, valves and pump

> Should have manual as well as auto release mechanism

> Activation shall give a visual and audible alarm in the protected space.